LIGHTING : - RECOMMENDED ILLUMINANCE LEVELS (BOILER, BREWERIES, CHEMICAL, CHOCLATE, GLASS)




   
VI) BOILER HOUSE (INDUSTRIAL)  
a) Coal and ash handling 100
b) Boiler rooms :  
1) Boiler fronts and operating areas 100+
2) Other areas 20 to 50
c) Ourdoor plants :  
1) Cat-walks 20
2) Platforms 50
   
   
VII) BREWERIES AND DISTILLERIES  
a) General working areas 150
b) Brew house, bottling and canning plants 200
c) Bottle inspection  Special lighting
   
   
VIII) CHEMICAL WORKS  
a) Hand furnaces, boiling tanks stationery driers, 150
stationery or gravity crystallizers, mechanical driers,   
evaporators, filtration plants, mechanical crystallizing,   
bleaching, extractors, percolators nitrators and electrolytic cells  
b) Controls, guages, valves, etc 100
c) Control rooms :  
1) Vertical control panels 200 to 300
2) Control desks 300
   
   
IX) CHOCOLATE AND CONFECTIONERY FACTORIES  
a) Mixing , blending and boiling 150
b) Chocolate husking, winnowing, fat extraction, crushing and 200
refining, feeding, bean cleaning, sorting, milling and cream  
making  
c) Hand decorating, inspection wrapping and packing 300
   
   
XI) GLASS WORKS AND PROCESSES  
a) Furnace rooms, bending, annealing lehrs 100
b) Mixing rooms, forming (blowing, drawing, pressing and rolling) 150
c) Cutting to size, grinding, polishing and roughening 200
d) Finishing (bevelling, decorating, etching and silvering) 300
e) Brilliant cutting 700
f) Inspection:  
1) General 200
2) Fine 700
   

No comments: